Stack lights with Modbus-RTU RS485 communication protocol

colonne_luminose

Connection module for modular stack light with Modbus RTU (RS485) communication protocol

Ideal for reducing the complexity and cost of electrical wiring. Facilitates the connection to many PLCs and SCADA (business supervision programs)

A perfect system for precise, summary and schematic indications that enable quick viewing and acquisition.

The best solution to inform the operator about machine status when changing production parameters.

It transforms a light-signalling device in a vertical developing synoptic form.

The Modbus protocol has been adopted in many industries sectors due to the following advantages:

  • user-friendliness;
  • system reliability;
  • high immunity to external noises;

Modbus RTU protocol is widely used due to its open source code that can be used royalty-free on any application or device.

The system features are explained in the instruction manual. For those wishing to develop their own application software, all the necessary tips and information are available.

General features

Any standard 370 series module powered by 24 V dc can be driven.

Communication protocol: Modbus RTU (RS485)

Maximum number of stackable modules: 7 for each terminal unit.

Light signalling: each light module can be individually programmed for steady or flashing operating with different flashing frequencies depending of the Modbus register value.

Acoustic signalling: the audio device can be programmed to emit a continuous or pulse tone with intermittent frequency sounds depending on the Modbus register value.

Connections: With screw clamps or via an M12- 5 pins circular connector.

Protection degree: IP65 (if properly mounted with cover and seal) according to EN 60529.

Resistance to vibrations: 2 days min. (10- 150 Hz) according to EN 60068-2-6.

Operating temperature: -20° / + 50°

Material: Policarbonate

colonne_luminose

Electrical Wiring Diagram

Colonne luminose - Texelco

Main connector:

  • Connect 24V DC and GND for power supply
  • Connect the cables for 485 port to the respective clamps following the description between PLC and/or 485/USB adapter

Diagnostics:

flashing LEDs: system running without errors

steady LEDs: an error according to the table below

DIAG1

DIAG2

DIAG3

Description

ON

OFF

OFF

Internal memory initialization error

OFF

ON

OFF

Software configuration loading error

ON

ON

OFF

PAY ATTENTION: Modbus in default configuration

OFF

OFF

ON

Error: Modbus system not in operation

ON

OFF

ON

Error: Modbus system restart failed

OFF

ON

ON

Error: Outputs not enabled

ON

ON

ON

Error: Non-working WiFi


Default:

If the jumper is inserted, the default settings are always as follows

Port speed: 9600 bps
Serial port configuration: 8 data bits, EVEN parity (even), one stop bit
Modbus mode: RTU

Modbus mapping

The system has 3 sets of Modbus registers described below
Register adress 0 (PLC 40001): 7 registers, from 0 to 6 (PLC 40001 to 40007) to check the status of the 7 outputs. The accepted values are:

Value

Description

0

Corresponding output OFF

1

Corresponding output ON (lighted lamp)

2

Flashing every 500 ms

3

Flashing every 1 s

4

Flashing every 2 s

254

Flashing according to value set in corresponding register 16

 

Register adress 16 (PLC 40017): 7 registers, from 0 to 6 (PLC 40017 a 40023) to check the flashing frequency if the output is set to 253.

Accept any value from 0 to 65535 ms.

Register adress 32 (PLC 40033): 4 registers setting Modbus parameters

40033 : set the baudrate, values may be:

0=110 bps
1=300 bps
2=600 bps
3=1200 bps
4=2400 bps
5=4800 bps
6=9600 bps
7=14400 bps
8=19200 bps
9=38400 bps
10=57600 bps
11=115200 bps
12=128000 bps
13=256000 bps

40034: set the Modbus mode

0=RTU
1=ASCII

40035: sets the slave adress
40036: sets parity, values can be

0=no parity
1=even
2=odd